@article{oai:kindai.repo.nii.ac.jp:00007341, author = {崔, 軍 and 湊, 政樹}, issue = {45}, journal = {近畿大学工学部研究報告, Research reports of the Faculty of Engineering, Kinki University}, month = {Dec}, note = {[Synopsis] Although the buildings which use a wall radiation heating system have been increasing recently, there are few papers about it. When indoor PMV was kept a constant value, the vrtical temperature distribution of wall radiant heating and the air conditioner heating was examined by experiments, and the following results were shown in this paper. (1)When indoor PMV is maintained by the same value, vertical temperature distribution of wall radiant heating (panel surface temperature 41℃ and 45℃) is larger than air conditioner heating (setting room temperature 22℃ and 24℃). (2)Air conditioner heating tends to produce horizontal temperature distribution than wall radiant heating. (3)Vertical temperature distribution of wall radiant heating is almost fixed regardless of the temperature of a radiant panel., application/pdf}, pages = {41--47}, title = {〈研究論文〉同様なPMV が保たれた場合における壁放射暖房とエアコン暖房の上下温度差に関する研究}, year = {2011}, yomi = {ミナト, マサキ} }