Department of Architecture, Faculty of Engineering, Kinki University
TODA Corporation
版
publisher
出版者 名前
近畿大学工学部
出版社 カナ
キンキ ダイガク コウガクブ
出版社 ローマ字
Kinki daigaku kogakubu
出版年(from)
2011
出版年(to)
12-20
日付 作成日
2012-03-03
雑誌名
近畿大学工学部研究報告
雑誌名(英)
Research reports of the Faculty of Engineering, Kinki University
号
45
ページ
41 - 47
発行年
2011-12-01
ISSN
0386491X
抄録
[Synopsis] Although the buildings which use a wall radiation heating system have been increasing recently, there are few papers about it. When indoor PMV was kept a constant value, the vrtical temperature distribution of wall radiant heating and the air conditioner heating was examined by experiments, and the following results were shown in this paper. (1)When indoor PMV is maintained by the same value, vertical temperature distribution of wall radiant heating (panel surface temperature 41℃ and 45℃) is larger than air conditioner heating (setting room temperature 22℃ and 24℃). (2)Air conditioner heating tends to produce horizontal temperature distribution than wall radiant heating. (3)Vertical temperature distribution of wall radiant heating is almost fixed regardless of the temperature of a radiant panel.